Sales / Products

Series Type KL: Specification
Series Type KL: Discharge Data
Series Type KM: Specification
Series Type KM: Discharge
Series Type KH: Specification
Series Type KH: Discharge

L Range

The L Range is designed for applications where the battery is required to provide energy over relatively long discharge period. Typical uses are power back-up and bulk energy storage.
- 11 to 1500 A/h in Plastic Cases
- 11 to 1650 A/h in Steel Cases

The M range

The M range is designed for applications where the batteries are required to sustain electrical loads for between 30 mins to 3 hours or for mixed loads which involves a mixture of high and low discharge rates. The range is typically used in power back-up applications.
- 11 to 1250 A/h in Plastic Cases
- 11 to 1250 A/h in Steel Cases

The H range

The H range is designed for applications where there is a relatively high current over a short periods, usually less than 30 mins in durations. The range is typically used in starting and power back-up applications.
- 10 to 250 A/h in Plastic Cases

Capacity

The nominal rated capacity C5 of a cell is the capacity in ampere hours (A/H) available at the 5-hour discharge rate to 1.0 volts/cell, in accordance with DIN EN 60623 and IEG 623. Nominal Voltage is 1.2 volts/Cell.

Charging

In general all standard charging methods with W-, I-, IU-characteristics are possible.

Constant Voltage Charging

Float Voltage range: 1.40 to 1.42 Volts/cell
Equalizing voltage range: 1.55 to 1.65 Volts/cell

Charging Output Current

The maximum charging output current is 2.5 I5 at 25C, provided that the charging Voltage Limit is not higher than 1.68 volts/cell. The minimum recommended charging rate is 110.

Constant Current Charging

Standard charge: 15 for 7 to 8 hours
Fast recharge: 215 for 2.5 hours,
Followed by: 1.5 for 2 to 3 hours
Minimum effective rate: I .5mA.IAh
Temperature coefficient: -3 to -4m V/0C
The electrolyte temperature should never
exceed 450C during charging.